User Tools

Site Tools


steam:profibusnet:start

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
steam:profibusnet:start [2021/07/11 16:23]
brinkhaus
steam:profibusnet:start [2021/07/23 10:34] (current)
brinkhaus
Line 1: Line 1:
 To be able to use a modified file in the Simatic Manager, the following applies: To be able to use a modified file in the Simatic Manager, the following applies:
  
-a) The file must have a different ​output status ​in the file name.+a) The file must have a different ​release date in the file name.
  
 b) If necessary, you have to force the Simatic Manager to use the modified file by placing a hash in front of the "​HILSCHER"​ in the file name. Then again you have to be careful when selecting the GSDML file to always click on the correct file version. b) If necessary, you have to force the Simatic Manager to use the modified file by placing a hash in front of the "​HILSCHER"​ in the file name. Then again you have to be careful when selecting the GSDML file to always click on the correct file version.
Line 11: Line 11:
 </​code>​ </​code>​
  
 +c) Main change in the Hilscher GSDML files 64byteoutput --> 128byteoutput;​ check areas around those points, too for "​64"​
 +
 +d) When programming with Sycon NET:
 +- Begin with a new (empty) project
 +- Add from the standalone slaves the target device to the horizontal grey line
 +- Click on "​configuration"​ on the new device
 +- Configure TCP on Settings/​Driver/​NetXDriver
 +- Enable in Settings/​Driver the NetXDriver
 +- Check card in device assignment